Notice - product not recommended for new projects.
It is planned to systematically decrease APZ production in favour of new device - APZplus.
The APZ family is designed for HV, MV and LV switchgears, supplying mainly non-motorized load, where voltage measurement is based on voltage transformers.
Possibility of operating up to 10 circuit breakers
Features of APZ automatic unit:
- Dedicated for circuit breaker systems (can operate in switchgears with number of circuit breakers from 2 to 10, with possibility of power supply from power generator);
- Designed to work on each voltage level (HV, MV and LV);
- It performs synchronous switching without interruption;
- Has the ability to switch circuit breakers on the upper side of the transformer supplying the switchgear;
- Configured individually
Automatic change-over unit (APZ) can perform the change-over in the following cycles:
- Automatic Transfer of Reserve (ATS) free caused by opening of circuit breaker in supplying line;;
- Automatic Power Switching (SZR) slow caused by voltage drop on busbars with closed breaker in supplying line;
- Scheduled Power-Up Transfer (PPZ) synchronous uninterruptible;
- Planned Power-Up Transfer (PPZ) synchronous uninterruptible; Planned Power-Up Transfer (PPZ) free;
- Return Flow Scheduling (RPS) synchronous uninterruptible;
- Automatic Reverse Power Switching (ARP) - synchronous uninterruptible; Automatic Reverse Power Switching (ARP) - slow;
- Automatic Power Switching (AZZ) slow